Identifying Critical Risks of Cascading Failures in Power Systems

Abstract

Potential critical risks of cascading failures in power systems can be identified by exposing those critical electrical elements on which certain initial disturbances may cause maximum disruption to power transmission networks. In this work, we investigate cascading failures in power systems described by the direct current (DC) power flow equations, while initial disturbances take the form of altering admittance of elements. The disruption is quantified with the remaining transmission power at the end of cascading process. In particular, identifying the critical elements and the corresponding initial disturbances causing the worst-case cascading blackout is formulated as a dynamic optimization problem (DOP) in the framework of optimal control theory, where the entire propagation process of cascading failures is put under consideration. An Identifying Critical Risk Algorithm (ICRA) based on the maximum principle is proposed to solve the DOP. Simulation results on the IEEE 9-Bus and the IEEE 14-Bus test systems are presented to demonstrate the effectiveness of the algorithm.

0

Turn this paper into a lesson

ArcXiv compiles a structured reading guide from this paper's metadata: plain-English importance, contributions, prerequisite concepts, which sections to read first, flashcards, and a quiz. Grounded in the abstract, never invented.

Discussion (0)

Sign in to join the discussion.

Loading comments…