Structural Impact of Grid-Forming Inverters on Power System Coherency

Abstract

This paper addresses the following fundamental research question: how does the integration of grid-forming inverters (GFMs) replacing conventional synchronous generators (SGs) impact the slow coherent eigen-structure and the low-frequency oscillatory behavior of future power systems? Due to time-scale separated dynamics, generator states inside a coherent area synchronize over a fast time-scale due to stronger coupling, while the areas themselves synchronize over a slower time scale. Our mathematical analysis shows that due to the large-scale integration of GFMs, the weighted Laplacian structure of the frequency dynamics is preserved, however, the entries of the Laplacian may be significantly modified based on the location and penetration levels of the GFMs. This can impact and potentially significantly alter the coherency structure of the system. We have validated our findings with numerical results using the IEEE 68-bus test system.