Dynamic Equivalent Identification of Interconnected Areas Using Disturbance records from Synchro phasor Measurement Units

Abstract

In this paper, a methodology for modelling a dynamic equivalent of an external area is presented. The equivalent consists of a generator with series impedance and a parallel load (generalized Ward equivalent), integrating control systems such as the Automatic Voltage Regulator (AVR) and the Speed Regulator (GOV) in a test system known as PST-16. The main objective is to identify the parameters of the control systems and other parameters inherent to the generator so that the response of the equivalent system is similar to the response of the complete system.

0

Turn this paper into a lesson

ArcXiv compiles a structured reading guide from this paper's metadata: plain-English importance, contributions, prerequisite concepts, which sections to read first, flashcards, and a quiz. Grounded in the abstract, never invented.

Discussion (0)

Sign in to join the discussion.

Loading comments…