Dynamic Equivalent Identification of Interconnected Areas Using Disturbance records from Synchro phasor Measurement Units
Abstract
In this paper, a methodology for modelling a dynamic equivalent of an external area is presented. The equivalent consists of a generator with series impedance and a parallel load (generalized Ward equivalent), integrating control systems such as the Automatic Voltage Regulator (AVR) and the Speed Regulator (GOV) in a test system known as PST-16. The main objective is to identify the parameters of the control systems and other parameters inherent to the generator so that the response of the equivalent system is similar to the response of the complete system.