Switching Transients in Constrained Transformer-Line/Cable Configurations
Abstract
This paper investigates the transient phenomena that occur in two special cases in the Netherlands: (A) during the energization of a power transformer via a cable feeder and (B) the energization of a power transformer together with an overhead line (OHL). In Case A a 7 km long 150 kV cable and a 150/50 kV transformer are connected and energized at the same time. In Case B a 150/50 kV transformer and a short 50 kV OHL are connected and energized simultaneously. The reason behind this kind of situations is related to space restrictions and cost efficiency.
Turn this paper into a full lesson
ArcXiv compiles a staged curriculum from this paper: 8-12 lessons across beginner → advanced, synthesised section guides, visuals, flashcards, a quiz, exercises, and on-demand deep dives per section. Grounded in the abstract, never invented.