Real-time Load Current Monitoring of Overhead Lines Using GMR Sensors
Abstract
Non-contact current monitoring has emerged as a prominent research focus owing to its non-intrusive characteristics and low maintenance requirements. However, while they offer high sensitivity, contactless sensors necessitate sophisticated design methodologies and thorough experimental validation. In this study, a Giant Magneto-Resistance (GMR) sensor is employed to monitor the instantaneous currents of a three-phase 400-volt overhead line, and its performance is evaluated against that of a conventional contact-based Hall effect sensor. A mathematical framework is developed to calculate current from the measured magnetic field signals. Furthermore, a MATLAB-based dashboard is implemented to enable real-time visualization of current measurements from both sensors under linear and non-linear load conditions. The GMR current sensor achieved a relative accuracy of 64.64% to 91.49%, with most phases above 80%. Identified improvements over this are possible, indicating that the sensing method has potential as a basis for calculating phase currents.
Turn this paper into a lesson
ArcXiv compiles a structured reading guide from this paper's metadata: plain-English importance, contributions, prerequisite concepts, which sections to read first, flashcards, and a quiz. Grounded in the abstract, never invented.