CT Saturation Detection and Compensation: A Hybrid Physical Model- and Data-Driven Method

Abstract

Current transformer (CT) saturation is one of the dominant causes of relay protection devices' malfunctions, which pose a threat to the safe operation of the power system. To address this problem, we propose a hybrid physical model- and data-driven method. The method firstly detects the CT saturation and then compensates it to reproduce the real waveform. Considering the multi-factor and strong nonlinearity of CT saturation, a data-driven model, namely the Fully Convolutional Network (FCN), is built to detect the operation status of CT. As for the compensation, a physical model of short-circuit current is used for its conciseness and universality. Through tactfully integrating the data model and the physical model, the proposed method is endowed with two major merits: the arduous adjustment of universal thresholds and parameters in existing methods is avoided, and the deficiency in generalization and interpretability of the data-driven method is assuaged. Simulation and experimental results verify the effectiveness of the proposed method. Furthermore, its application potential to future protection is explored.

0

Turn this paper into a lesson

ArcXiv compiles a structured reading guide from this paper's metadata: plain-English importance, contributions, prerequisite concepts, which sections to read first, flashcards, and a quiz. Grounded in the abstract, never invented.

Discussion (0)

Sign in to join the discussion.

Loading comments…