Construction and Measurements of an Improved Vacuum-Swing-Adsorption Radon-Mitigation System

Abstract

In order to reduce backgrounds from radon-daughter plate-out onto detector surfaces, an ultra-low-radon cleanroom is being commissioned at the South Dakota School of Mines and Technology. An improved vacuum-swing-adsorption radon mitigation system and cleanroom build upon a previous design implemented at Syracuse University that achieved radon levels of 0.2\,Bq\,m-3. This improved system will employ a better pump and larger carbon beds feeding a redesigned cleanroom with an internal HVAC unit and aged water for humidification. With the rebuilt (original) radon mitigation system, the new low-radon cleanroom has already achieved a >\,300× reduction from an input activity of 58.60.7\,Bq\,m-3 to a cleanroom activity of 0.130.06\,Bq\,m-3.