Measurement and simulation of two-phase CO2 cooling for the AFTER electronics of the Micromegas modules for a Large Prototype of a Time Projection Chamber

Abstract

The readout electronics of a Micromegas (MM) module consume nearly 26 W of electric power, which causes the temperature of electronic board to increase upto 70\, C. Increase in temperature results in damage of electronics. Development of temperature gradient in the Time Projection Chamber (TPC) may affect precise measurement as well. Two-phase CO2 cooling has been applied to remove heat from the MM modules during two test beam experiments at DESY, Hamburg. Following the experimental procedure, a comprehensive study of the cooling technique has been accomplished for a single MM module by means of numerical simulation. This paper is focused to discuss the application of two-phase CO2 cooling to keep the temperature below 30\, C and stabilized within 0.2\, C.