A Closed-Loop Thermal Dynamic Model for AI Data Center Cooling Load Simulation

Cletus Ngwerume, Lang Tong, Chee-Wooi Ten, Yi Hu

eess.SY

Abstract

Accurate modeling and simulation of cooling electricity demand is essential for characterizing AI data center loads, but time-synchronized operational measurements are scarce. Constant coefficient-of-performance models can oversimplify cooling behavior, while detailed thermal state-space models are cumbersome to use. This paper proposes a closed-loop simulation framework that couples a linear thermal dynamic model with deadband-based control to capture nonlinear cooling behaviors. The framework is validated against operational data from the Marconi100 supercomputer. Compared with the baseline, the proposed model reduces the mean absolute error from 95.80 to 23.52 kW and the root-mean-square error from 109.79 to 29.91 kW. The statistical evaluation further shows improved reproduction of daily peak demand and intraday variability. The framework provides a computationally tractable approach to generate physically interpretable cooling load profiles for power system studies.