Abstract
Low-voltage ride-through (LVRT) forces a grid-following inverter to allocate finite converter current between active- and reactive-current objectives. This paper uses a PSCAD electromagnetic-transient (EMT) representation of an aggregated battery energy storage system (BESS) to quantify how short-circuit ratio (SCR) and grid impedance X/R ratio alter that tradeoff. Active-current priority and reactive-current priority are compared for five paired grid conditions under the same 150-ms balanced three-phase fault, with pre-fault active power approximately 0.84 pu, POI reactive-power exchange near 0 pu, and a 1.0-pu dq-current limit. Fundamental positive-sequence voltage and power are reconstructed from 100-s three-phase EMT outputs. Across the fixed-fault SCR sweep, the Q-priority late-fault voltage advantage increases from 0.046 pu in the strongest tested grid to 0.129 pu in the weakest; the weakest P-priority case also shows active-power reversal and a pronounced controller-frequency excursion. At fixed SCR, changing X/R produces a smaller increase from 0.092 to 0.112 pu, mainly through reduced P-priority voltage support. Because the common physical fault also deepens the passive retained-voltage condition as SCR decreases, the SCR result is interpreted as a fixed-fault grid-strength sensitivity rather than a constant-sag comparison. Grid strength is the larger sensitivity in the tested matrix, while X/R remains an additional modifier under the studied fault conditions.
Create a lesson
Metadata
- Categories
- eess.SY, cs.SY
- Comments
- 6 pages, 4 figures. Accepted for presentation and publication at the 2027 IEEE Texas Power and Energy Conference (TPEC 2027)
Related papers
Advanced Reactance Method - A Novel Approach for Distance Protection in Presence of Grid-Following Inverter-Based-Resources
Shared title terminologyeess.SYJonathan Loebel, Jannik Polster, Johann Jaeger
Dynamic Modeling of Transmission Networks, Grid-Following Inverters, and UPS-Based AI Data Centers
Shared title terminologyeess.SYMuhammad Hamza Ali, Amritanshu Pandey
Measurement-Based Assessment of Decadal Inertia and Primary Frequency Response Trends in the US Eastern Interconnection
Shared title terminologyeess.SYSaurav Dulal, Mark Baldwin, Narges Ghiasi et al.
Asymptotically Efficient Finite Impulse Response System Identification without Noise Knowledge
Shared title terminologyeess.SYZichen Liu, Biqiang Mu
DynaSeek: Large Language Model-Driven Hybrid Dynamic Model Discovery for Grid-Tied Inverters from Limited Measurements
Shared title terminologyeess.SYHongwei Zhen, Chao Shen, Jianfeng Niu et al.
Voltage-Feedback Backoff and Restoration for Priority-Based EV Charging Control
Shared title terminologyeess.SYEyad Alsulayhim, Ning Lu