Control-Layer Interpretation of Reactive Power Recovery Limits in EMT-RMS Model Benchmarking of Inverter-Based Resources
Dileep Cheerla, Amirthagunaraj Yogarathnam, Divya Jain, Satish Natti
Abstract
EMT--RMS benchmarking is widely used to verify cross-platform consistency of inverter-based resource (IBR) dynamic models. This paper examines a 200 MW anonymized IBR represented in PSCAD and PSS/E. The EMT model separates inverter electrical capability from a plant-level power plant controller (PPC) recovery target, whereas the RMS model represents these functions through REECC and REPCA parameters. Directly assigning the PPC target of pu to REPCA hard reactive limits is initialization-inconsistent at the original lagging operating point because the initial reactive command is 0.396273 pu. A second, near-unity-power-factor operating point initializes successfully with the same diagnostic limit, demonstrating that the conflict is operating-point dependent. Using the non-conflicting capability mapping removes the original hard-limit conflict, but the benchmark still shows 18.5--30.2 MVAr post-event POI reactive-power differences from PSCAD. A one-at-a-time REPCA sensitivity under matched benchmark initial conditions further shows that RMS recovery is parameter- and limit-dependent: at and 0.10 the aggregate machine reactive output reaches the configured capability bounds, while moves VDOWN, VUP, and HVRT off those bounds and changes their settled POI reactive power by 8.94, 18.00, and 3.17 MVAr, respectively. Machine-to-POI accounting further shows why machine-side saturation need not reproduce the POI-level PPC recovery magnitude. The results distinguish initialization feasibility from recovery equivalence and provide a control-layer diagnostic workflow beyond waveform comparison.
Create a lesson
Metadata
- Categories
- eess.SY, cs.SY
- Comments
- Accepted for presentation at IEEE PES Grid Edge Technologies 2027, April 19-22, 2027, Salt Lake City, Utah, USA.5 pages, 3 figures, 6 tables
Related papers
Power-Swing Blocking and Out-of-Step Tripping Scheme Using the Swing Center Voltage in Systems With Inverter-Based Resources
Shared title terminologyeess.SYHenrik Johansson, Qianli Xing, Jaekeun Lee et al.
Power-Swing Blocking Scheme Based on Continuous and Higher-Order Incremental Quantities for Systems with Inverter-Based Resources
Shared title terminologyeess.SYHenrik Johansson, Qianli Xing, Nathaniel Taylor et al.
Protection challenges and solutions on power systems towards 100% inverter-based resources and energy storage systems
Shared title terminologyeess.SYAlexander Novikov, Luis A. Garcia-Reyes, Anup Joshi et al.
LC-Resonance Placement Limits and Damping Recovery in Virtual-Admittance-Based Grid-Forming Inverter Control
Shared title terminologyeess.SYStephen Arinze Obi, Jae-Jung Jung
Damping Ratio and Convergence Rate Analysis for Inverter-Based Power Systems via Root Locus
Shared title terminologyeess.SYDan Wang, Wei Chen, Yan Jiang et al.
Overcoming Fundamental Control Limitations in Powered Descent Flight through Robust Incremental Nonlinear Dynamic Inversion
Shared title terminologyeess.SYJoão T. Diz, Paulo Rosa, Pedro Simplício et al.