Assessing Data Center Hosting Capacity Considering Electromagnetic Transient Dynamics
Fan Jiang, Xingpeng Li
Abstract
Hosting capacity is commonly assessed with steady-state optimization, which leaves the dynamic response of the data center and the grid at the resulting operating point untested. This paper assesses candidate data center capacities by coupling a unit commitment (UC) model with electromagnetic transient (EMT) simulation. During the capacity search, the UC model determines the economic dispatch for each tested data center capacity, and the resulting operating points are tested for settling with the generators committed online by the UC model and after a selected synchronous generator outage. Three nested capacities are obtained: the optimization-based steady-state capacity, the dynamic pre-outage capacity, and the post-outage dynamic capacity, each bounded by the previous one. On a test system with a detailed data center model, both dynamic capacities fall well below the optimization capacity, and the ranking of connection locations changes with the assessment stage and with the outage. In the most severe outage case at each candidate bus, the capacity is about 30% below the steady-state capacity. Thus, the dynamic response of the data center and the grid should be part of the hosting capacity assessment, and the comparison of connection locations should be made on the post-outage dynamic capacity.
Create a lesson
Related papers
N-1 Security constrained Hosting Capacity Assessment for Ultra Large-scale Data Center with Workload Flexibility
Shared title terminology · Jiakai Wu, Pengyu Ren, Yifan Wang et al.
AC Assessment of DC Power Flow Screening for Data Center Hosting Capacity and Siting
Shared title terminology · Haoxiang Wan, Jesus Silva-Rodriguez, Jonghwan Kwon et al.
Quantifying the hosting capacity value of workload flexibility for AI data centers: A two-stage electricity-computation co-optimization framework
Shared title terminology · Jiakai Wu, Wei Sun, Pengyu Ren et al.
Which Data-Center Load Models Can Be Trusted? An Evidence-Graded Review of Dynamic Modeling and Validation for Large Computational Loads
Shared title terminology · Dileep Cheerla
A Dynamic Model and Stability Analysis of a Grid-Interactive Data Center
Shared title terminology · Advith Natarajan, Xinyang Zhou, Guido Cavraro
Modeling and Stability of Power Systems With Coupled Data Center and Grid Dynamics
Shared title terminology · Guido Cavraro