Closed-Form Formula for dcritical(a0)d_{\mathrm{critical}}(a_0) in Large Fully Connected Power Grids

Sachin Kadloor

math.PR

Abstract

Kadloor and Santhi (arXiv:1011.4098) modeled cascading failures in a large fully connected power grid by a coupled four-variable recursion for the minimum surviving load ana_n, the mean failed load μn−1μ_{n-1}, the redistributed load Dn\mathcal{D}_n, and the stagewise failure probability pnp_n. They noted that the recursion was not tractable and identified the critical disturbance dcriticald_{\mathrm{critical}} by simulation. We show that the recursion telescopes exactly into a one-dimensional monotone map an+1=g(an)a_{n+1} = g(a_n). This yields the threshold in closed form: 1−a0=dcritical (1+ln⁡(1+1/dcritical))1 - a_0 = d_{\mathrm{critical}}\,(1 + \ln(1 + 1/d_{\mathrm{critical}})), or explicitly in terms of the lower branch W−1W_{-1} of the Lambert W function. We prove a sharp dichotomy. For dm≤dcriticald_m \le d_{\mathrm{critical}} the cascade halts with limiting load a0+dcriticala_0 + d_{\mathrm{critical}} at criticality and surviving fraction 1/(1+dcritical)1/(1 + d_{\mathrm{critical}}). For dm>dcriticald_m > d_{\mathrm{critical}} a complete outage occurs in finitely many steps.