Identifiability-Guided Composite Load Modeling of AI Data Centers
Abstract
The rapid growth of AI data centers introduces large, workload-dependent loads whose protection and reconnection behavior can affect power-system transient stability. Calibrating dynamic models of such loads is challenging because treating all associated elements as freely estimable may lead to weakly identified or physically confounded parameterizations. This paper proposes an identifiability-guided calibration framework for a composite load model with separate IT, cooling, and auxiliary branches. A nuisance-projected Fisher-information criterion characterizes the local identifiability of the cooling-motor composition, while a workload non-equivalence result shows that voltage-only recalibration cannot reproduce workload-dependent responses. Guided by these results, a grey-box estimator trained with branch-level supervision learns the workload-to-power relation and the cooling composition, while retaining a prescribed UPS protection law and an externally anchored reconnect-ramp duration. The learned workload relation is then distilled into a closed form for transient-stability simulation. Evaluation using 300,000 MIT Supercloud GPU power-utilization samples and 12,600 IEEE 39-bus fault scenarios yields an aggregate active-power of 0.948, compared with 0.856 for an LSTM baseline. Removing branch-level supervision preserves relatively high aggregate accuracy but substantially degrades cooling-component recovery. Under unseen deep voltage sags, the proposed model achieves a transient of 0.750, compared with 0.033 for the LSTM. Closed-loop simulations further show that cooling composition and protection behavior can affect retained-load states and voltage responses near protection thresholds.
Create a lesson
Metadata
- Categories
- eess.SY, cs.SY
Related papers
Data Center-Aware Load Pickup in Power System Restoration
Shared title terminologyeess.SYYousef Abudyak, Saleh Sadeghi Gougheri, Mohsen Alizadeh et al.
Which Data-Center Load Models Can Be Trusted? An Evidence-Graded Review of Dynamic Modeling and Validation for Large Computational Loads
Shared title terminologyeess.SYDileep Cheerla
Thermal-Guided Ensemble Reinforcement Learning for Regime-Adaptive Short-Term GPU Power Forecasting in AI Data Centers
Shared title terminologyeess.SYYuanshuo Zhang, Ying Zhang, Ziying Wang et al.
Physics-Guided Multi-Output Surrogate Modeling of a Centralized-UPS Data Center
Shared title terminologyeess.SYJesus D. Vasquez-Plaza, Sunil Subedi, Jin Dong et al.
Data Center Load Accommodation under QoS and Checkpoint-Induced Frequency Security Constraints
Shared title terminologyeess.SYRuolan Cui, Ziang Liu, Chenxi Hu et al.
Impact of Data Center Load on Co-Optimized Generation and Transmission Expansion Planning with Embedded Unit Commitment
Shared title terminologyeess.SYHaoxiang Wan, Xingpeng Li, Jonghwan Kwon