One number per hour is not enough: directional carbon intensity of data-center ramps on the PJM fleet
Abstract
A data-center campus can change its load by hundreds of megawatts within an hour, yet every carbon signal in use gives one value per hour for a load change, whatever its size or direction. We compute the directional carbon intensity, the emission caused or avoided per megawatt-hour of a finite upward or downward ramp, for every hour of 2025 on the PJM Interconnection's fossil fleet, and compare it with the locational marginal emission rate (LME) and the regional average. The LME misstates a 1 GW ramp by more than 10% in 60% to 83% of hours in eleven months. Upward and downward ramps differ in a quarter to three quarters of hours but agree on their monthly mean. Location-based reporting assigns 47% to 59% of a ramp's emission to other consumers. A campus should schedule on the signal for its ramp's size and direction and report the emission it causes.
Create a lesson
Related papers
Which Data-Center Load Models Can Be Trusted? An Evidence-Graded Review of Dynamic Modeling and Validation for Large Computational Loads
Shared title terminology · Dileep Cheerla
Data-center growth impacts household electricity costs more through wholesale prices than through grid reinforcement
Shared title terminology · Lingdong Zhou, Wenjia Xia, Jiyu Wang et al.
Reducing Data-Center Load Transfers with Ride-Through-Aware Voltage Control
Shared title terminology · Siyu Lu, Yang Weng
Unlocking Heterogeneous Accelerator Flexibility in AI Data Centers: Sizing and Workload Allocation
Shared title terminology · Chenghao Lyu, Ying Yu, Wangkun Xu et al.
Thermal-Guided Ensemble Reinforcement Learning for Regime-Adaptive Short-Term GPU Power Forecasting in AI Data Centers
Shared title terminology · Yuanshuo Zhang, Ying Zhang, Ziying Wang et al.
Physics-Guided Multi-Output Surrogate Modeling of a Centralized-UPS Data Center
Shared title terminology · Jesus D. Vasquez-Plaza, Sunil Subedi, Jin Dong et al.