Sub-Synchronous Control Interaction Risk of Large Data Center Loads: A Frequency-Scan Assessment with Cross-Model Validation
Salish Maharjan, Junyuan Zheng, Lung-An Lee, Min Lwin, Zhaoyu Wang
Abstract
Data centers are now one of the fastest-growing loads on the bulk power system, and most of their demand reaches the grid through power converters inside uninterruptible power supplies (UPS). Whether these loads can take part in sub-synchronous control interaction (SSCI), as wind and HVDC converters do, has not been studied extensively. We examine this question with impedance-based frequency scans at the point of common coupling (PCC). Using a detailed proprietary model (INS-ISU), we scan the motor, variable-frequency-drive (VFD), lighting, and UPS-fed information-technology (IT) branches of a representative facility separately. Only the UPS in double-conversion mode shows negative resistance; it covers the whole sub-synchronous band and continues up to about 170 Hz. The other branches, and the UPS in bypass mode, stay passive. We then repeat the scans on three public models from PNNL, TAMU, and NLR. None of them shows negative resistance in bypass mode, while three of the four models do in double-conversion mode. Lowering the load from rated to light load makes the negative resistance deeper, as expected for a constant-power load, so a lightly loaded facility in double-conversion mode is the worst case. Raising the UPS DC-link capacitance pushes the negative resistance into a narrow band around the fundamental. These findings give a basis for screening data centers for SSCI during interconnection studies.
Create a lesson
Related papers
Which Data-Center Load Models Can Be Trusted? An Evidence-Graded Review of Dynamic Modeling and Validation for Large Computational Loads
Shared title terminology · Dileep Cheerla
N-1 Security constrained Hosting Capacity Assessment for Ultra Large-scale Data Center with Workload Flexibility
Shared title terminology · Jiakai Wu, Pengyu Ren, Yifan Wang et al.
Low-Voltage Ride-Through in AI Data Centers via Coordinated Battery and Computing Load Control
Shared title terminology · Xiaoyang Wang, Xin Chen, Fang Chen Lin et al.
Grid-Forming AI Data Centers: Coordinated Grid Support Control from IT Loads and Energy Storage
Shared title terminology · Xuechun Zhang, Zhiyi Zhao, Fei Teng et al.
DC Voltage Control Dominated Oscillations in Electromechanical Frequency Range - Insights from Synchronous Coefficient Reduction Effect of IBR Plants and Network Interactions
Shared title terminology · Qiang Fu, Siqi Bu
Rented Oscillations: Multi-Tenant Data Center Workload Synchronization Attacks and Mitigation
Shared title terminology · Zaint A. Alexakis, Li Zhou, S. Gokul Krishnan et al.