Low-Voltage Ride-Through in AI Data Centers via Coordinated Battery and Computing Load Control
Xiaoyang Wang, Xin Chen, Fang Chen Lin, Prasad Enjeti, Ali Yazdanpanah, Yunzhi Cheng, Shri Abhyankar
Abstract
The ability of large AI data centers to ride through grid voltage sags is critical to power system stability and reliability. This paper frames data center low-voltage ride-through (LVRT) as a DC-link power balance problem. Once the rectifier reaches its current limit, the power drawn from the grid decreases in proportion to the grid voltage. The DC-link capacitor can supply the resulting power deficit only briefly before the DC-link voltage falls low enough to trigger undervoltage protection tripping. To address this issue, this paper proposes effective control strategies for coordinating uninterruptible power supply (UPS) battery and computing load curtailment to offset the power deficit and enable LVRT at minimum control cost. Three control scenarios are studied: UPS battery support alone, computing load curtailment alone, and the coordinated use of both resources. Electromagnetic transient (EMT) simulations using the TAMU-ERCOT AI data center model demonstrate that battery support and the coordinated strategy achieve LVRT for all tested sags, including a near-zero-voltage fault, while load curtailment alone rides through moderate voltage sags.
Create a lesson
Related papers
Model-Free UPS Control Tuning for Improved Low-Voltage Ride-Through in AI Data Centers
Shared title terminology · Haowen Xu, Xin Chen
Grid-Forming AI Data Centers: Coordinated Grid Support Control from IT Loads and Energy Storage
Shared title terminology · Xuechun Zhang, Zhiyi Zhao, Fei Teng et al.
Which Data-Center Load Models Can Be Trusted? An Evidence-Graded Review of Dynamic Modeling and Validation for Large Computational Loads
Shared title terminology · Dileep Cheerla
Sub-Synchronous Control Interaction Risk of Large Data Center Loads: A Frequency-Scan Assessment with Cross-Model Validation
Shared title terminology · Salish Maharjan, Junyuan Zheng, Lung-An Lee et al.
Quantifying the hosting capacity value of workload flexibility for AI data centers: A two-stage electricity-computation co-optimization framework
Shared title terminology · Jiakai Wu, Wei Sun, Pengyu Ren et al.
Locational Marginal Pricing of Compute: Co-optimizing Compute and Energy for Transparent Data Center Flexibility
Shared title terminology · Vladimir Pyltsov, Teng Zeng