AI Agents Executing an RMS and EMT Ride-Through Workflow on a 2,000-Bus Synthetic Texas Grid: A Case Study with Open-Source Tools
Tam Kemabonta, Brighton Ombuki, Vladimir Abdelnour
Abstract
This paper reports a case study of engineer-supervised AI agents executing a predefined RMS and EMT ride-through workflow on the 2,000-bus ACTIVSg2000 synthetic Texas grid with open-source tools. The test case is a 133 MW battery with a co-located 130 MW data-center load, assessed against ride-through criteria fixed before simulation and for loss of synchronism elsewhere in the grid. One agent ran 44 RMS cases and 15 without-project comparisons in ANDES; the other ran a 220-row EMT intake bench and an 84-row system study in DPsim and ParaEMT on a Kron-reduced area. Across the 44 RMS cases, 127 criterion cells fail, including loss of synchronism in all 44. Two findings concern the project plant. The battery keeps absorbing reactive power during sags on the light-load schedule (B3, as low as -19.8 Mvar on S4 T1), and the data-center load returns only at 5.00-5.56 s after long bolted faults (L3), which misses the ERCOT load-return requirement. In 13 of the 15 comparisons, which the authors selected after slips or speed-gate stops, the same machines slip without the project; the other 29 runs have no without-project comparison. RMS and EMT values differ in network, plant model, controls, operating point, and base, and so they are reported as separate, unaligned observations. The paper reports the errors the authors identified in the agent logs, 63 author messages, and 3.8 days from agent start to the integrated study report. The agents executed and documented the predefined ride-through and stability workflow, which covers one part of an interconnection study.
Create a lesson
Related papers
Comparison of Open-Source PSCAD EMT Models for Large-Scale AI Data Centers in Smart Grids
Shared title terminology · Alex Chen, Ahmad Mohammad Saber, Deepa Kundur
EPIGRIDS: Documentation and Validation of Seven Open Synthetic Transmission Grid Cases
Shared title terminology · Jonathan M. Snodgrass, Scott Greene, Thomas J. Overbye et al.
Benchmarking a Grid Foundation Model for AC Optimal Power Flow: Feasibility and Warm-Start Results on Synthetic Texas and South Carolina Grids
Shared title terminology · Tam Kemabonta, Brighton Ombuki, Vladimir Abdelnour
Low-Voltage Ride-Through in AI Data Centers via Coordinated Battery and Computing Load Control
Shared title terminology · Xiaoyang Wang, Xin Chen, Fang Chen Lin et al.
Model-Free UPS Control Tuning for Improved Low-Voltage Ride-Through in AI Data Centers
Shared title terminology · Haowen Xu, Xin Chen
Hierarchical Agentic Mid-Band Agility for Reliable Low-Latency Space-Air-Ground Integrated V2X Networks
Shared title terminology · Liu Cao, Zisheng Gong, Lyutianyang Zhang et al.